UPS System 20kVA

DESCRIPTION
UPS SYSTEM composed by 2 Unit that works in parallel, complete of battery charger and control of the
batteries state
NOMINAL POWER: 20 kVA
INPUT LINE: 3ph 440V 60Hz
OUTPUT LINE / POWER:

  • Output 3ph 1: 115V 60Hz – 15,5 kVA
  • Output 3ph 2: 115V 400Hz – 2,2kVA
  • Output line 3: 24V DC – 2,5 kW

BYPASS Option (separate cabinet)
THE UNIT GUARANTEE THE FOLLOWING OUTPUT LINES IN CASE OF BOTH UPS UNITS FAULT:

  • Output 3ph 1: 115V 60Hz
  • Output line 3: 24V DC

DIMENSIONS
WDH [mm] 620x500x350 (without resilient)
MASS
MAX 75 Kg

MAIN PROJECT STANDARDS REFERENCES

  • MIL-STD-810 (Environmental conditions)
  • MIL-STD-461 (EMC)
  • MIL-STD-167-1 (Vibration) – TESTED
  • MIL-STD-740 (Noise)
  • MIL-S-901 (Shock) – F.E.A. Analysis

COOLING SYSTEM
FORCED AIR
IP GRADE
IP56
ELECTRIC INTERFACE
TERMINAL BOARDS & GLANDS
SYSTEM
UPS SYSTEM (15-30 minutes)

Key Points

  • Low magnetic signature
  • Each UPS unit provides the required power rate, the system works also with only one UPS operative

 

Sector & Platform

 

Product data sheet

Maintenance Plus

Eurocontrol offers a new and exclusive system support service directly to end users, thus obtaining many significant benefits: minimize the cost of downtime, maximize the uptime service, extend the equipments’ operational life, resolve problems independently, swiftly and effectively, balance supply and depot costs.

Do you need a taylor made solution?

Thanks to our team of highly trained and experienced application engineers, we can solve even highly complex problems.